Trace Upgrade for Systems (1575e and NexSys)

Trace Upgrade for Systems (1575e and NexSys)

Trace Sensor Kit

The Trace Sensor Kit is used for additional Trace Chemistry control to the Lakewood Instruments model 1575e and NexSys Systems cooling tower controllers. The Trace Mounted Sensor Kit includes an Inline Fluorometer, an inline tee, a pre-wired isolator, a power supply, and a calibration cell.

The Inline Fluorometer is a low cost, compact fluorometer designed for monitoring of fluorescent dyes in industrial water systems. Integration of the inline Fluorometer into your 1575e automation system enables monitoring of fluorescent trends in real time for better control of your cooling water chemistry. The fluorometer is designed as a rugged, 24/7 device providing maximum performance, minimal maintenance and solid-state reliability.

Trace Mounted Sensor Kit shown with a Model 1575e Cooling Tower Water Treatment Controller on A Mounting Plate.

1575e Displaying Trace PPM
1575e Displaying Trace setpoint range

Features

  • Includes a single-channel fluorometer that provides a 4-20 mA analog signal output that is directly proportional to the concentration of your traced chemistry.

  • Solid-state LED/Photodiode technology, no moving parts

  • A low maintenance design to provide trouble-free performance.

  • Includes a pre-wired isolator to eliminate power supply interference.

  • Includes an in-line tee for use in light industrial environments.

  • Includes a second tee to be used for calibration purposes without having to remove the in-line tee.

  • Works with PTSA fluorescent dye

  • Probe output is pre-calibrated (base and slope) at 200 ppb trace @20mA. Using a 1 to1000 PTSA mix equates to 100 ppb of trace equaling 100 ppm of chemical in system.

Benefits

  • Easy to add to the Lakewood Instruments Model 1575e and the NexSys Series cooling tower controllers in the field. Firmware upgrade allows older 1575e units to accept this new technology. Note: Signal Conditioning is not available when used with the 2000e Series of controllers.

  • Easy to transition to Trace Chemistry Control using Lakewood Instruments control schemes.

  • Installs into your process flow with a PVC tee.

  • Comes preset and aligned at the factory.

Specifications

Material
PVC Type 1
Range (Calibrated)
0 - 200 ppb (Trace)
Threading
1 Inch NPTF
Output Signal
4-20 mA
Max Pressure
100 psi
Input Voltage
8 TO 30 vdc
Max Temperature
140ºF (60ºC)

 

METEX CORPORATION LIMITED

About Us

Metex Corporation Limited has been providing superior products and services to the process control, chemical treatment, waste water, industrial and manufacturing industries for over 25 years. It is our goal to continually provide our customers with the best possible equipment, technology, and service.

Sitemap

Our Products

Dataloggers, sensors, pumps, recorders, hand held instruments, flow instrumentation, level controls, valves, instrumentation, containers, tanks, transmitters, data loggers, digital indicators, mixers and agitators, pressure intrumentation, analyzers and controllers for a variety of industrial applications such as water quality, pH/ORP and more.

Website Content

Water Analyzers and Controllers, Wireless Products, Corrosion Monitoring Equipment, Cooling Tower and Boiler Controllers, a wide variety of Pumps, Valves, Dataloggers and Recorders, HVAC, Instrumentation, Skids and Systems, Containers and Tanks from world leading manufacturers are products you will find on this site.

Get in Touch