Search This Site

(Search by Product Type i.e. Level or Brand Name i.e. Walchem)

Mighty Modules Model SR2101 DC Input
Isolated Field Rangeable Two Wire Transmitter

ORDERING INFORMATION
SR2101, ( )
| (examples)
| 0/10 V
| 1/5  V
| -1/1  V
| 4/20 mA
| Input Range

Example: SR2101,0/10V

DC,Input,Isolated,Field,Rangeable,Two,Wire,Transmitter,Model SR2101,Wilkerson Instrument Catalogue
DC,Input,Isolated,Field,Rangeable,Two,Wire,Transmitter,Model SR2101,Wilkerson Instrument Manual



Features
DC,Input,Isolated,Field,Rangeable,Two,Wire,Transmitter,Model SR2101,Wilkerson Instrument Provides DC Output Proportional to a DC Voltage or Current Input
DC,Input,Isolated,Field,Rangeable,Two,Wire,Transmitter,Model SR2101,Wilkerson Instrument Fully Isolated Input/Output
DC,Input,Isolated,Field,Rangeable,Two,Wire,Transmitter,Model SR2101,Wilkerson Instrument Unlimited
DC,Input,Isolated,Field,Rangeable,Two,Wire,Transmitter,Model SR2101,Wilkerson Instrument Choice of Input Ranges via Interchangeable Range Cards
DC,Input,Isolated,Field,Rangeable,Two,Wire,Transmitter,Model SR2101,Wilkerson Instrument Reverse Polarity-Protected
DC,Input,Isolated,Field,Rangeable,Two,Wire,Transmitter,Model SR2101,Wilkerson Instrument Test Points for Loop Current Monitoring Without Breaking Loop Circuit
DC,Input,Isolated,Field,Rangeable,Two,Wire,Transmitter,Model SR2101,Wilkerson Instrument 50 mm Diameter Case - 33 mm Mounting Hole Spacing
DC,Input,Isolated,Field,Rangeable,Two,Wire,Transmitter,Model SR2101,Wilkerson Instrument NEMA-4 and Explosion-Proof Connection Heads Available
DC,Input,Isolated,Field,Rangeable,Two,Wire,Transmitter,Model SR2101,Wilkerson Instrument Low Cost
DC,Input,Isolated,Field,Rangeable,Two,Wire,Transmitter,Model SR2101,Wilkerson Instrument 5 + 5 Year Warranty


Description

The SR2101 is a low-cost, reliable, DC input two-wire transmitter for field or panel mounting in various industrial housings and enclosures. It provides a DC output current (4/20 mA) proportional to a voltage or current input.  The output is galvanically isolated from the input.

The SR2101 includes filtering and conditioning to reduce susceptibility to transients and noisy operations.  It uses a feedback VCO to develop a pulse train with a duty cycle proportional to the input signal amplitude.  This pulse train is coupled through a pulse transformer to the output circuitry, where the duty cycle data is converted to a proportional 4/20 mADC output level.  A plug-in range card permits user ranging to the required voltage or current input range.  The output ZERO and SPAN controls are accessible through the top of the case.  Zero is adjustable ± 20% and span +5/-55%.  Terminations are made to screw  terminal connectors on top of the case.

Test points located on the SR2101 front panel allow monitoring of loop current value, using a milliammeter, without breaking the loop current.

Typical Application

Remote data acquisition.  Voltage to current conversion and isolation. Elimination of ground loops and common mode signals.

Mounting

The SR2101 can be mounted in a connection head (TSH-A6L), explosion-proof housing (XJAY), or on a flat surface using the two 4.5 mm diameter mounting holes provided. Standard 33 mm hole center spacing allows for mounting in most connection heads. The 5.08 mm center hole allows clearance for input wiring.  An optional DIN-Rail mounting kit is available (DMP2000).

Specifications

INPUT RANGE
Voltage
  any range between ± 128 V max
  (minimum full scale span 16 mV)
Current
  (internal shunt)
  any range between ± 0.1 A max
  (minimum full scale span 10 µA)

OUTPUT RANGE
4/20 mA
  Current limited = 28 mA

RESPONSE TIME
- Step Change
150 ms for 99% of final value

OFFSET CANCEL
can cancel any offset from
-100% to +100% of span

INPUT IMPEDANCE
V In < 1 V: > 10 megohms
V In > 1 V: >  1  megohm

I In: range dependent:

Current Input:
Input Shunt Value:

0/1   mA
0/5   mA
4/20  mA
10/50  mA
0/100 mA

100.0 ohms
49.9 ohms
61.9 ohms
20.0 ohms
20.0 ohms
COMMON MODE REJECTION
120 dB, DC to 60 Hz

OPERATING TEMPERATURE
-13°F to 176°F
-25°C to  80°C

MAX LOAD RESISTANCE (kilohms)
=[(V supply - 10)/20 mA]

TEMPERATURE STABILITY
± 0.015% of span per°C

LINEARITY
Better than ± 0.05% of span

ACCURACY
± 0.1% of span

POWER
10-36 VDC, polarity protected

ISOLATION, OUTPUT TO INPUT
1000 Volts RMS sinewave

SUPPLY VOLTAGE EFFECT
0.02% of span max, 10 to 36 V

 

*Within specified range limits

METEX CORPORATION LIMITED

About Us

Metex Corporation Limited has been providing superior products and services to the process control, chemical treatment, waste water, industrial and manufacturing industries for over 25 years. It is our goal to continually provide our customers with the best possible equipment, technology, and service.

Sitemap

Our Products

Dataloggers, sensors, pumps, recorders, hand held instruments, flow instrumentation, level controls, valves, instrumentation, containers, tanks, transmitters, data loggers, digital indicators, mixers and agitators, pressure intrumentation, analyzers and controllers for a variety of industrial applications such as water quality, pH/ORP and more.

Website Content

Water Analyzers and Controllers, Wireless Products, Corrosion Monitoring Equipment, Cooling Tower and Boiler Controllers, a wide variety of Pumps, Valves, Dataloggers and Recorders, HVAC, Instrumentation, Skids and Systems, Containers and Tanks from world leading manufacturers are products you will find on this site.

Get in Touch