Lakewood Model 1575e Conductivity Controller
PART NUMBER 1229242 SHOWN-Cooling Tower Water Treatment Controller, Including Flow Switch Plumbing And Conductivity Sensor On A Mounting Plate
Features
-
Removable power cord and receptacles for simple conduit installations.
-
Scheduled feed, which can use three relays for biocides or other chemicals.
-
Two (2) water meter inputs, two (2) drum switch inputs, conductivity input, a flow switch input, a 4-20 mA output, and a 4-20 mA input are all standard features.
-
The 4-20 mA input can be used with a transmitter for one of the following: remote conductivity, makeup conductivity, pH, ORP, percent, pressure, milliamps, flow rates, or traced chemistry control. This transmitter can be added in the field.
-
Designed with a single circuit board for better reliability and lower cost.
-
Large open shallow enclosure for easy wiring.
-
Ball valve delay feature allows accurate control of motorized ball valves.
-
Heavy-duty stainless steel domed numeric keypad and illuminated graphical display allow for quick and easy programming. Steel domed switches improve the tactile sensing and life expectancy of the keypad. LED indicators for power, alarm and relay status.
Benefits
-
Easy to program with the Lakewood plain English, intuitive, and user friendly menu interface.
-
Controller can be used in boiler, cooling tower, or condensate applications when used with the appropriate conductivity sensor.
-
Single circuit board design improves reliability.
-
No add-on options. 4-20 mA output and feed schedule clock features are standard.
-
Conductivity range: 50-10,000 µS for cooling towers; 500-8000 µS for boilers; 10-100 µS for condensate
-
Conductivity sensor: 2 electrode
-
Conductivity Resolution: +/-10 µS (conductivity <5000 µS) +/-100 µS (conductivity > 5000 µS)
-
Temperature comp.: Automatic
-
Accuracy & repeatability: +/-1.0%
-
Deadband/Setpoint: Programmable
-
Auto/Manual outputs: Menu selectable
-
Keypad: 16 tactile push-buttons
-
Display: Illuminated 128x64 pixel LCD
-
Drum Switch Inputs: 2 digital contact inputs
-
Water meter inputs (2): Contact head, paddle wheel or turbine
-
Timers: Max. blowdown time exceeded and relay run time exceeded
-
Output Signal: One 4-20 mA, isolated or non-isolated optionally powered output for conductivity
-
Input Signal: One 4-20 mA, non-isolated internally powered input for conductivity
-
Output relays: 4, 3 selectable use, 1 blowdown
-
Relay ratings: 3A each, 10A total
-
Power: 120/240 VAC 50/60 Hz
-
Ambient: 32º- 120ºF (0 - 49ºC)
-
Enclosure: NEMA 4X
Sensors/Plumbing
|
Cooling Tower
|
Boiler
|
Condensate
|
Max Pressure
(at 100ºF) |
140 psi (9.65 bar) @100ºF |
600 psi (41.3 bar) |
70 psi (4.8 bar) |
Max Temp |
140ºF (60ºC) |
486ºF (252ºC) |
392ºF (200ºC) |
Min flow |
1 gpm (3.785 Lpm) |
Varies w/orifice plate |
1 gpm (3.785 Lpm) |
|
1229239 Water Treatment Controller only. Universal controller is field programmable for cooling towers, boilers, and condensate applications.
1229240 Water Treatment Controller, including Cooling Tower Sensor Tee and Conductivity Sensor.
1229241 Water Treatment Controller, including Cooling Tower Flow Switch Plumbing and Conductivity Sensor.
Cooling Tower Options
|
|
Cooling Tower Flow Switch Plumbing w/Sensor
|
Cooling Tower Sensor Tee and Conductivity Sensor
|
1167158 Cooling Tower sensor with 20 ft of cable.
1169440 Plumbing Tee.
1107003 Flow Switch Plumbing.
|
|
|
SR2 |
ORIFICE UNION
|
MBV1
|
1168374 SR2 Boiler water sensor with 20 ft cable and elbow. _ NPT connection.
1166355 Orifice Plate, _ in NPT, 1/16 - inch opening.
1166356 Orifice Plate, _ in NPT, 1/4 - inch opening.
1166354 Orifice Plate, _ in NPT, 1 /8 - inch opening.
1167972 Orifice Plate, _ in NPT, 3 /8 - inch opening.
1167244 Orifice Union, _ in NPT.
1166686 MBV1 _ in NPT Motorized ball valve.
1104591 540K.1-4-10I-10-TC500 Condensate sensor with _ in NPT inline fitting. 0-100 µS.
1168617 540K.1-4-10R-18-TC500 Condensate sensor with 1.0 in NPT retractable inline fitting. 0-100 µS.
1104592 540K.01-4-10I-10-TC500 Condensate sensor with _ in NPT inline fitting. 0-10 µS.
1169642 540K.01-4-10R-18-TC500 Condensate sensor with 1.0 in NPT retractable inline fitting. 0-10 µS.